Non-Compliance detail
Summary
Licence number:
2504
Annual Return Start:
01 Feb 2019
Annual Return End:
31 Jan 2020
Date Received:
27 Mar 2020
Licence Condition number
Type of non-compliance
EPA actions
No. of times occurred
L3
Exceedance of volume limit to Allens Creek (LDP24) during new water treatment plant IMS Stage 2A commissioning. 3460 & 3334 kL/day cf limit of 3000 kL/day. No identified environmental harm. Volume limits amended. New PRP added to EPL.
S.58 notice issued to change/amend licence conditions(s)
2
L2
LDP 22 BOD non-compliance, 56/96/137 cf limit of 50 mg/l discharge to irrigation. LDP 19 pH non-compliance 100 %, laboratory error. BOD due to power trip/low STP usage. Modifications made to effluent treatment system.
Appropriate Action taken by licensee
4
P1.3
Burst pipe resulting water discharging into Brennans Creek for a period of 6 hours. The water was the same as is usually discharged to the creek but came from a different point. No environmental consequence.
Appropriate Action taken by licensee
1
O2.1
Conductivity probe failure at Brennans Creek Dam (BCD). Probe used to activate Sydney Water dilution water discharge into Breenans Creek. Possibly due to contamination. A more frequent cleaning program for the probe has been implemented.
Appropriate Action taken by licensee
1
M2.2
Dust Deposition Gauge bottles were not changed out within 30+/-2 days, due to a delay in return of the bottles from the analytical laboratory. Spare bottles are now being kept on site.
Appropriate Action taken by licensee
1
O1, O2
Flocculant tank next to Brennans Creek not bunded. The EPA issued a Show Cause Notice on 17 April 2019. A Formal Warning Letter was issued on 3 June 2019. No discharge to Brennans Creek
EPA has written to licensee regarding non-compliance and relevant action
1